|
From
April 1st 2002 new Building Regulations come into
force , making great changes to the way that Installers must
work. Every time a boiler or hot water cylinder is changed, the
whole heating system must be checked and brought up to the new
standards of efficiency and control.
The
regulations themselves are written in a very open way, but they
refer to documents which give clear advice for any installer or
homeowner. The two main documents are The Good Practice Guide
302 (GPG302) and Central Heating Standard Specification (CheSS
– GIL059), these give two levels of control that will be
deemed to satisfy the regulations; “Good Practice” and
“Best Practice” .
What
is required?
- When
a boiler or cylinder is replaced, the whole heating system
must be checked and upgraded if necessary. This will ensure
that the boiler will be able to work to its declared
efficiency. (There is no point in fitting a new highly
efficient boiler on an inadequate system).
- The
new boiler or cylinder must meet efficiency standards –
SEDBUK for the boiler BS for the cylinder. (Medium duty
cylinders DO NOT satisfy these).
- For
the system to be compatible with the higher efficiency
boilers, it should be fully pumped.
- The
system must have a boiler interlock.
- If
a bypass circuit is fitted, an automatic bypass valve must
be used. (Slumber or Bypass radiators are only acceptable on
solid fuel systems).
- The
controls fitted should be either Good or Best practice as
defined in CheSS or GPG302)
- When
completed the system must be commissioned to ensure that all
components are installed and functioning properly.
- When
the system is handed over to the householder, operation and
maintenance must be explained to the user and instructions
left with proof of commissioning. ( A completed and signed Benchmark
Logbook is accepted).
Controls
requirements are laid out below. For more details, see CheSS or
GPG302.
Good
Good Practice
Stored
Hot Water Systems
Programmers
(Preferred
with independent times for CH/DHW)
Room Thermostat
Cylinder Thermostat
Motorised Valve (s)
Radiator thermostats throughout*
Automatic Bypass Valve**
Combi Boilers
Timeswitch
Room thermostat
Radiator thermostats throughout*
Automatic Bypass Valve**
Best Practice
Stored Hot
Water Systems
Programmable
room thermostat with capability to control DHWRoom thermostat
Cylinder thermostat
Motorised valve (s)
Radiator thermostats throughout*
Automatic bypass valve**
Combi Boilers
Programmable
room thermostat
Radiator thermostats throughout*
Automatic bypass valve**
*
Radiator thermostats should be used on all radiators except
where the room thermostat is fitted.
**
If a bypass circuit is used, then an automatic bypass valve must
be fitted.
For
stored hot water systems, Sundial S, W and Y Plans satisfy Good
practice and Smartfit satisfies Best Practice.
On
Combi systems, use ST6100 and a room thermostat for Good
Practice and a programmable thermostat for Best Practice.
Documentation:
TACMA - A new
guide - How to comply with the revised building regulations
2001/2002. This guide supports the official guidance
covering the use of controls in boiler based, gas and oil fired
domestic central heating installations within the revised
Building Regulations, Part L1 for England & Wales and Part J
for Scotland.
Click here to read.
Guidance notes from the Energy Efficiency Partnership for
Homes entitled "The Domestic Heating & Hot Water Guide
to the Building Regulations 2001 - Part L1" is available
from the DTLR - Click
here to read.
A
leaflet on the Building Regulations Part L1 will be available in
all merchants.
Click here to read.
Benchmark
Logbook.
Click here to read.
Visit
the TACMA website to download a copy of the Building Regulations
Part L1.
Click here to visit.
|